Question 19. What has to appear on the fire control plan?
Your Answer:
(Not answered)
Correct Answer:
C (the layout of each deck, the fire divisions and where the detecting and extinguishing gear stands, the whole agreeing with what is there)
💡 The plan is written for the people coming to fight the fire, so it must answer where to get in, what will stop the fire spreading, with what it is to be attacked and how to get out: the decks as arranged and numbered, the boundaries of class A and class B divisions and the fire zones they make, the doors and the dampers, the detection and the alarm, the systems and the appliances with where each stands, the ventilators and the means of closing them, and the ways of escape. It is made of durable material, agrees with the ship as she now is, and is altered when she is altered; a copy stands outside the bridge for the shore brigade and a copy is kept with the company. Hence marking only the extinguishers, the company settling the style, or a general arrangement drawing in place of it all fail - that drawing carries no line of fire division, no detection or extinguishing gear, and is not revised with the work. Each note on the plan is compared with the thing itself, and the commonest finding is the change that was made without the plan being changed.